The new RHÖN-KLINIKUM Campus Bad Neustadt - the hospital of the future!

|   Air filter technology

LAF ceilings for a total of 30 operating theatres and intervention rooms in the H1a and H1b room classes as well as four instrument prep zones – quite an impressive number indeed.

At the end of 2018 a large project was completed and put into operation by the clinic: Marchhart equipped no less than 30 operating theatres and intervention rooms in the H1a and H1b room classes as well as four instrument prep zones with air filtering systems to ensure optimal clean room ventilation. Reflecting the H1b respectively H1a room class we installed the LAF supply air or LAF circulated air ceilings with horizontal filtering layers and HEPA filter outlets with stainless steel extraction air ducts, matching fans, collecting ducts with integrated cooling coils, suction modules and corresponding control cabinets, rectangular air extraction cabinets for HCU equipment, triangular air extraction cabinets with integrated fluff separators and other accessories.

The RHÖN-KLINIKUM Campus Bad Neustadt clinic is a cross-sector healthcare provider for the rural region. In addition to core medical services the clinic also offers health care and services which have so far been spatially separated – non-hospital specialists, the clinic, rehabilitation and nursing. The aim is to make the treatment noticeably easier for the patients.

The Marchhart installation frames for structurally integrated LED lighting were also included; they will ensure optimal illumination of the operating area along with comfortable ambient lighting. We also installed triangular and rectangular ECCO LINE air extraction cabinets with fluff separators with the "EASY-CLICK" system and our proprietary modular air extraction cabinets specifically designed for HCU equipment.

Technical key data:
Completion of our project: end of 2018

Clean room air extraction cabinets type: Ma-RR-ABLS 400x 165/ stainless steel, with integrated fluff separator with "EASY-CLICK" system, for concealed wall mounting; 
3 LAF supply air ceilings with horizontal filtering layer type: Ma-LF-ZP 3.2*3.2(e)/horizontal, made completely of stainless steel, "Ma-VSG-SS" stabilising apron for LAF supply air diffuser, height: 200mm, glazing: laminated safety glass 8mm, fine aluminium frames, powder coated in RAL 9010; 
11 LAF supply air ceilings with horizontal filtering layer type: Ma-LF-ZP 2.4*1.8 (e)/horizontal, completely made of stainless steel including HEPA filters, framing for ambient lighting/L-shaped; mounting frames for structural ambient lighting (Trilux/Fidesca PM 412/1248 LED / ETDD);
4 LAF circulated air ceilings: Ma-LF-ZP-U 2.6*1.7(e)/horizontal, completely made of stainless steel, "Ma-VSG-SS" stabilising apron for LAF supply air diffuser, height: 680 mm, glazing: laminated safety glass 8mm, fine aluminium frames, powder coated in RAL 9010; each with two ceiling recirculation modules DUM 1.5 (1,500 m³/h); material: highly airtight welded aluminium including pre-filters; suction respectively pressure sound absorbing elements as well as fluff separators in the suction area; 
4 control cabinets for two recirculated air modules / for each complete recirculated air ceiling system;
63 HEPA filter outlets in standard height respectively flat design;
43 clean room air extraction cabinets, triangular, dimensions 700 x 350mm and 500 x 250mm, with integrated top and bottom fluff separators; 
8 clean room air extraction cabinets, 800 x 1000mm, made of stainless steel for HCU equipment, in modular sandwich design;
3 clean room air extraction cabinets, rectangular, dimensions 350 x 150 mm, with integrated top and bottom fluff separators; 
94 fluff separators, type ECCO LINE MR-V2A slot sliders in various sizes and designs;