Recirculated air ceiling systems for Alexianer St. Hedwig Kliniken Berlin

|   Air filter technology

In the course of extending and modernising the Alexianer clinic we equipped four operating theatres with recirculated air ceiling systems with integrated cooling.

The hospital is the oldest catholic hospital in Berlin and symbolises tradition with a future. In the course of extending and modernising the clinic we equipped four operating theatres with recirculated air ceiling systems with integrated cooling.

We used LAF recirculated air ceilings type Ma-LF-ZP 2.4 x 2.4 m/H14/DUM 1250-4/KÜ 5.09kW per operating theatre (three systems) and type Ma-LF-ZP 3.2 x 3.2 m/H14/DUM 1250-8/KÜ 10.24kW per operating theatre (one system) with horizontal filtering layer in H14 filter class, appropriate fans, collecting ducts with integrated cooling coils (designed for “dry cooling”), suction modules and corresponding control cabinets. The ambient lighting frames guarantee optimal illumination of the operating area and comfortable lighting conditions. A total of thirteen triangular and three rectangular extraction air cabinets with type Ma-FA-ECCO-LINE fluff separators with the "EASY-CLICK" system along with F7 class pre-filters positioned behind them were installed in the four operating theatres, with the installation taking up as little space as possible.

Technical key data:
Completion of our project: 13th of September 2018
Hygienic acceptance by the accredited AW-Weynert Berlin hygiene institute: 12th of October 2018

Equipment:
4 complete recirculated air cooling ceiling systems, each comprised of:
LAF supply air ceiling, recirculation system, collecting ducts, extraction air ducts, illumination frames for ambient lighting
DUM 1250-4 respectively DUM 1250-8 fan modules
ASM 2.0 collecting duct with coolers 4x 1.27kW, total 5.08kW, and
ASM 3.0 collecting duct with coolers 4x 2.56kW, total 10.24kW, (cooling coil designed for dry cooling)
BASIS control cabinet type 0.6
13 extraction air cabinets with fluff separators and pre-filters, stainless steel, triangular 
3 extraction air cabinets with fluff separators and pre-filters, stainless steel, rectangular 
 

Go to the FAQ page for more details on recirculated air ceilings >>